ZQPT Arresters
Print This Page

"ZQPT"
Available for System Voltages Up to 345kV

Users of electricity have become more and more demanding over recent years.  The quality of the power they receive is critical to their operations.  Sensitive electronic equipment cannot tolerate voltage fluctuations and many problems are directed to the utility.  The heightened awareness of power quality has brought the issue to all levels of operations including transmission.

In the area of transmission line power quality, MPS offers the "ZQPT" transmission line arrester.  The lightweight construction makes it possible to easily mount arresters on the transmission line structures.  The arresters provide a preferred path between line and ground, guarding against insulator flashover.

Surge protection of transmission lines is a solution to troublesome outages and customer dissatisfaction.  State-of- the-art protection of transmission lines using polymer MOV arresters provides higher power quality, which will improve customer satisfaction.

"ZQPT" transmission line arresters are available for system voltages up to 345kV.  The metal oxide blocks are specially selected and wrapped under compression with a strong fiberglass wrap.

Application:
"ZQPT" transmission line arresters are applied to:

  • Improve power quality and overall line performance
  • Supplement shield wire protection
  • Provide protection for lines without a shield wire
  • Create more space on structures by eliminating the shield wires
  • Protect both new construction and retrofit

The factors that impact transmission line lightning performance include the following:  The amount of lightning activity in a given area per year, the stroke magnitude and the wave shape of the lightning, the tower height and the amount of nearby natural shielding from trees or buildings, the tower footing resistance, the presence of an overhead shield wire and the shield angle, and the existing line insulation.

When selectring transmission line arresters for specific application, there are several things to keep in mind.  The application is usually different for a line with an overhead shield wire than without.  The arrester rating should be coordinated with the arresters in the substation.  The transmission line arresters should be the same rating or larger so that they do not end up protecting the substation arresters.

The transmission line arresters should be sized by evaluating the line voltage and the line insulation.  By using a high MCOV arrester the temporary overvoltage (TOV) capability will be increased and the energy capability will also be greater.  With the added lightning exposure that may be expected on a transmission line, it is helpful to have higher capabilities in these categories.  Also, higher rated arresters will not experience as much duty because the reference voltage is higher and they will not turn on as soon as lower rated units.

Benefits:

Lightning is one of the major causes of power interruption.  Currently, shield wires serve as lightning protection for transmission lines.

"ZQPT" transmission line arresters provide these advantages over the use of shield wire alone.

  • Minimize the requirement to lower ground resistance
  • Protect against backflash
  • Safeguard from induced surges caused by nearby lightning
  • Limit effects of switching surges
  • Install easily and economically
  • Allow for reduction of structure BIL
  • Reduce system breaker operations
  • Provide protection for isolated problem areas
  • Improve overall line performance
  • Enhance customer relations

 

 

Features:

English Metric

ZQPT Electrical Characteristics
Catalog Number Voltage Rating (Ur) (kV rms) MCOV (Uc) (kVrms) Equivalent F.O.W. kV (Crest) Switching Surge kV (crest) Discharge Voltage (1.5kA) Discharge Voltage (3kA) Discharge Voltage (5kA) Discharge Voltage (10kA) Discharge Voltage (20kA) Discharge Voltage (40kA) Creepage (in) Weight Ea (lbs) length B (in) Strike (in)
8155CS0036 36 29.0 130.2 84.9 95.1 98.5 104.1 115.5 131.3 155.1 53 10.8 19.5 20.5
8155CS0039 39 31.5 134.7 87.8 98.4 101.9 107.8 119.5 135.9 160.5 53 10.8 19.5 20.5
8155CS0045 45 36.5 156.8 102.2 114.5 118.6 125.4 139.0 158.1 186.8 65 12.7 23.3 24.3
8155CS0054 54 42.0 195.8 127.7 143.0 148.1 156.7 173.7 197.5 233.3 78 14.7 27.0 28.0
8155CS0060 60 48.0 217.3 141.7 158.7 164.4 173.9 192.8 219.2 258.9 78 14.7 27.1 28.1
8155CS0066 66 54 226.4 147.6 165.4 171.3 181.1 200.8 228.3 269.7 91 17.8 33.1 34.1
8155CS0072 72 57.0 261.5 170.5 191.0 197.8 209.2 231.9 263.7 311.5 116 21.6 40.6 41.6
8155CS0090 90 70.0 326.0 212.6 238.1 246.6 260.8 289.1 328.8 288.3 116 21.7 40.6 41.6
8155CS0096 96 76.0 347.5 226.6 253.8 262.9 278.0 308.2 350.5 414.0 130 24.8 46.6 47.6
8155CS0108 108 88 391.1 255.0 285.6 295.9 312.9 346.9 394.5 465.9 143 26.7 50.4 51.4
8155CS0120 120 98.0 434.6 283.5 317.5 328.8 347.7 385.5 438.4 517.8 155 28.7 54.2 55.2
8155CS0132 132 106 478.8 312.3 349.7 362.2 383.0 424.7 783.0 570.4 194 35.7 67.6 68.6
8155CS0144 144 115 521.8 340.3 381.1 394.8 417.4 462.8 526.3 621.6 194 35.7 67.7 68.7
8155CS0172 172 140 620.8 404.9 453.5 569.7 496.7 550.7 626.2 739.6 272 49.6 94.6 95.6
8155CS0180 180 144 653.1 425.9 477.0 494.1 522.5 579.3 658.8 778.2 272 49.8 94.6 95.6
Notes:
1)  * The equivalent Front-of-Wave is the maximum discharge voltage for a 10kA impulse current wave
        which produces a voltage wave cresting in 0.5
μs
2)  ** Based on a switching surge current of 500 amperes for arresters rated 36kV to 90kV , and 1000
      amperes for arresters 108kV to 240kV.
3)  Transmission line arresters are application specific.  Contact your MacLean Power representative for
      additional information.
 

ZQPT Physical Data
Catalog Number Voltage Rating (Ur) (kV rms) Creepage (in) Weight Ea (lbs) A (in) B (in) Strike (in)
8155CS0036T**** 36 55 12 4.2 19.6 20.1
8155CS0039T**** 39 55 12 4.2 19.6 20.1
8155CS0045T**** 45 65 14 4.2 23.4 24.0
8155CS0054T**** 54 76 16 4.2 27.2 27.9
8155CS0060T**** 60 76 16 4.2 27.2 27.9
8155CS0072T**** 72 114 24 4.2 40.7 41.9
8155CS0090T**** 90 114 26 4.5 41.7 41.2
8155CS0096T**** 96 131 29 4.5 47.5 47.3
8155CS0108T**** 108 141 31 4.5 51.2 51.2
8155CS0120T**** 120 152 33 4.5 55.0 58.1
Notes:
1)  The **** identify the mounting hardware. (Application Specific)
 