Arresters >>
Secondary Arresters
|

|
|
|
Surge Tec® Secondary Arresters
|
 |

|
Features:
-
Surge Tec® arresters incorporate special features that make them stand above
other Secondary Arresters and Transient Voltage Surge Suppressors (TVSS).
-
These arresters use a patented (#5,502,612) fault withstand design along with
replacement indication.
-
The arresters are available in 175 volt, 480 volt and 650 volt AC ratings for
application on system voltages below 650 volts phase to ground and operate at
frequencies between 48 and 62 Hz.
-
The units come with 18 inch, #14 AWG solid copper wire leads and are
designed to be mounted outdoors or indoors.
-
FAULT WITHSTAND CAPABILITY - Surge Tec® secondary arresters' patented
design achieves a fault withstand capability of 10kA rms without the use of any
external fusing. This unique design has been tested at high current failure
modes to verify its ability to withstand a failure without a violent fracture of its
housing. Fault current is the full available current that the device conducts in the
event it is short circuited by conducting a surge beyond the designed capability.
This provides significant advantages in the area of secondary voltage protection.
-
REPLACEMENT INDICATION - A visual indication on the front label permits
routine checks of the arrester's operational status. Indication windows on the
label turn black if the arrester fails. The arrester should be replaced when any
area of any window turns black.
Application:
-
MacLean's Surge Tec® arresters are classified for category B and C installations
based on the diagram shown below.
-
The arresters are designed for repeated operation and continuous protection.
-
Surge arresters provide the path of least resistance to ground for surges on a
system. THE ARRESTERS SOULD BE INSTALLED BY A LICENSED
ELECTRICIAN.
-
To provide the best protection, the lead wires should be kept as short as
possible. When installed properly, they will divert lightning surges to ground very
quickly.
-
Surge Tec® arresters offer the first line of defense for the entire electrical service
and protect wiring, major appliances, pumps, and heating/air conditioning
equipment.
-
For added protection to computers, MacLean Power Systems recommends
a plug-in-strip type of device with lower clamping voltages as a second line of
defense. This type of coordination provides excellent surge protection for the
entire electric service.
|

- MacLean Power Guarantee - A one (1) year warranty is provided on all products manufactured.
| Catalog Number |
Fig. |
Voltage Rating MCOV |
Poles |
Energy Cap. (Joules/Phase) |
Response Time (nsec.) |
Front-of-Wave Protection Level (kV Crest) |
1.5kA |
5.0kA |
10kA |
Weight Oz. (Grams) |
|
Z1-175-0
|
1 |
175 |
1 |
427 |
<5 |
1.21 |
.747 |
.954 |
1.271 |
14 [435] |
|
Z2-175-0
|
1 |
175 |
2 |
427 |
<5 |
1.21 |
.747 |
.954 |
1.271 |
15 [466] |
|
Z3-175-0
|
2 |
175 |
3 |
427 |
<5 |
1.21 |
.747 |
.954 |
1.271 |
18 [560] |
|
Z1-480-0
|
2 |
480 |
1 |
742 |
<5 |
1.900 |
1.417 |
1.761 |
2.160 |
18 [560] |
|
Z2-480-0
|
2 |
480 |
2 |
742 |
<5 |
1.900 |
1.417 |
1.761 |
2.160 |
19 [590] |
|
Z3-480-0
|
2 |
480 |
3 |
742 |
<5 |
1.900 |
1.417 |
1.761 |
2.160 |
20 [622] |
|
Z1-650-0
|
2 |
650 |
1 |
919 |
<5 |
2.48 |
2.009 |
2.439 |
2.850 |
19 [590] |
|
Z2-650-0
|
2 |
650 |
2 |
919 |
<5 |
2.48 |
2.009 |
2.439 |
2.850 |
20 [622] |
|
Z3-650-0
|
2 |
650 |
3 |
919 |
<5 |
2.48 |
2.009 |
2.439 |
2.850 |
21 [653] |
| Catalog Number |
Fig. |
Voltage Rating MCOV |
Poles |
Energy Cap. (Joules/Phase) |
Response Time (nsec.) |
Front-of-Wave Protection Level (kV Crest) |
1.5kA |
5.0kA |
10kA |
Weight Oz. (Grams) |
|
Z1-175-0
|
1 |
175 |
1 |
427 |
<5 |
1.21 |
.747 |
.954 |
1.271 |
14 [435] |
|
Z2-175-0
|
1 |
175 |
2 |
427 |
<5 |
1.21 |
.747 |
.954 |
1.271 |
15 [466] |
|
Z3-175-0
|
2 |
175 |
3 |
427 |
<5 |
1.21 |
.747 |
.954 |
1.271 |
18 [560] |
|
Z1-480-0
|
2 |
480 |
1 |
742 |
<5 |
1.900 |
1.417 |
1.761 |
2.160 |
18 [560] |
|
Z2-480-0
|
2 |
480 |
2 |
742 |
<5 |
1.900 |
1.417 |
1.761 |
2.160 |
19 [590] |
|
Z3-480-0
|
2 |
480 |
3 |
742 |
<5 |
1.900 |
1.417 |
1.761 |
2.160 |
20 [622] |
|
Z1-650-0
|
2 |
650 |
1 |
919 |
<5 |
2.48 |
2.009 |
2.439 |
2.850 |
19 [590] |
|
Z2-650-0
|
2 |
650 |
2 |
919 |
<5 |
2.48 |
2.009 |
2.439 |
2.850 |
20 [622] |
|
Z3-650-0
|
2 |
650 |
3 |
919 |
<5 |
2.48 |
2.009 |
2.439 |
2.850 |
21 [653] |
Notes:
1) Add an "A" to obtain the mounting bracket (Z1-650-0A)
|
Typical Wiring Connections
| Maximum Phase-Phase/Phase-Ground Voltages |
| Maximum Phase-Phase/Phase-Ground Voltages |
|

|