S2 - 50 kip VX

S2–VX Series are Custom MPS Suspensions for 50k SML. End fittings, lengths, and leakage are designed to customer specific applications.

S2 Series Dim Drawing Image

English Metric

S2 Series

Catalog Number Dry Electrical Flashover (kV) 60 Hz Wet Electrical Flashover (kV) 60 Hz CIFO+ (kV) Neg (kV) CIFO Section Length (in) Dry Arc (in) Leakage (in) Weight Lbs (kg)
S2 40 80 073 VX SS 043 745 641 1243 1302 87.6 76.7 238.6 25.6 (11.6)
S2 40 80 070 VX SS 041 716 619 1198 1256 84.6 73.7 227.8 24.7 (11.2)
S2 40 80 073 VX SS 030 745 641 1243 1302 87.6 76.7 188.1 21.5 (9.8)
S2 40 80 070 VX SS 028 716 619 1198 1256 84.6 73.7 177.4 20.7 (9.4)
S2 40 80 067 VX SS 018 688 597 1154 1211 81.6 70.7 135.6 17.4 (7.9)
S2 40 80 067 VX SS 030 688 597 1154 1211 81.6 70.7 182.1 21.1 (9.6)
S2 40 80 064 VX SS 017 659 575 1109 1165 78.6 67.7 128.7 16.8 (7.6)
S2 40 80 064 VX SS 028 659 575 1109 1165 78.6 67.7 171.4 20.2 (9.2)
S2 40 80 061 VX SS 016 630 552 1063 1118 75.6 64.7 121.8 16.3 (7.4)
S2 40 80 061 VX SS 026 630 552 1063 1118 75.6 64.7 160.6 19.4 (8.8)
S2 40 80 058 VX SS 017 602 529 1018 1072 72.6 61.7 122.7 16.4 (7.5)
S2 40 80 058 VX SS 027 602 529 1018 1072 72.6 61.7 161.5 19.5 (8.9)
S2 40 80 055 VX SS 015 573 506 972 1025 69.6 58.7 111.9 15.6 (7.1)
S2 40 80 055 VX SS 025 573 506 972 1025 69.6 58.7 111.9 15.6 (7.1)
S2 40 80 052 VX SS 026 545 483 926 978 66.6 55.7 151.6 18.7 (8.5)
S2 40 80 049 VX SS 026 516 459 880 930 63.6 52.7 148.6 18.5 (8.4)
S2 40 80 052 VX SS 016 545 483 926 978 66.6 55.7 112.8 15.6 (7.1)
S2 40 80 046 VX SS 025 488 435 834 882 60.6 49.7 141.7 18 (8.2)
S2 40 80 049 VX SS 015 516 459 880 930 63.6 52.47 105.9 15.1 (6.9)
S2 40 80 043 VX SS 026 459 411 787 834 57.6 46.7 142.6 18.1 (8.2)
S2 40 80 046 VX SS 015 488 435 834 882 60.6 49.7 102.9 14.9 (6.8)
S2 40 80 040 VX SS 024 430 386 740 786 54.6 43.7 131.9 17.2 (7.8)
S2 40 80 043 VX SS 015 459 411 787 834 57.6 46.7 99.9 14.7 (6.7)
S2 40 80 037 VX SS 023 402 362 693 736 51.6 40.7 125.0 16.7 (7.6)
S2 40 80 040 VX SS 015 430 386 740 786 54.6 43.7 96.9 14.5 (6.6)
S2 40 80 037 VX SS 014 402 362 693 736 51.6 40.7 90.1 13.9 (6.3)
S2 40 80 034 VX SS 015 373 336 645 687 48.6 37.7 90.9 14 (6.4)
S2 40 80 034 VX SS 021 373 336 645 687 48.6 37.7 114.2 15.9 (7.2)
S2 40 80 031 VX SS 015 345 311 597 637 45.6 34.7 87.9 13.8 (6.3)
S2 40 80 031 VX SS 019 345 311 597 637 45.6 34.7 103.5 13.8 (6.3)
S2 40 80 028 VX SS 009 316 286 548 586 42.6 31.7 61.7 11.7 (5.3)
S2 40 80 028 VX SS 017 316 286 548 586 42.6 31.7 92.7 14.2 (6.5)
S2 40 80 025 VX SS 006 288 260 500 535 39.6 28.7 39.6 10.6 (4.8)
S2 40 80 025 VX SS 014 288 260 500 535 39.6 28.7 78.1 13 (5.9)
S2 40 80 022 VX SS 007 259 234 450 484 36.6 25.7 47.9 10.6 (4.8)
S2 40 80 022 VX SS 013 259 234 450 484 36.6 25.7 71.2 12.5 (5.7)
S2 40 80 019 VX SS 005 230 207 400 431 33.6 22.7 37.1 9.8 (4.4)
S2 40 80 019 VX SS 011 230 207 400 431 33.6 22.7 60.4 11.7 (5.3)
S2 40 80 016 VX SS 005 202 180 350 379 30.6 19.7 34.1 14 (6.4)
S2 40 80 016 VX SS 009 202 180 350 379 30.6 19.7 49.7 15.2 (6.9)
S2 40 80 013 VX SS 005 173 153 299 325 27.6 16.7 31.1 13.8 (6.3)
S2 40 80 013 VX SS 007 173 153 299 325 27.6 16.7 38.9 14.4 (6.5)

1)  Electrical Data is without Corona Rings. For Insulators 230kV and higher, MPS recommends
     use of Corona Rings.
2)  End fittings for listed catalog numbers = Y-Clevis / ANSI 52-11 Ball
3)  For other ratings or custom insulator designs, contact your local MPS Sales Representative.

S2 Series Continued... Dim Drawing Image

English Metric

S2 Series Continued...

Catalog Number Dry Electrical Flashover (kV) 60 Hz Wet Electrical Flashover (kV) 60 Hz CIFO+ (kV) Neg (kV) CIFO Section Length (in) Dry Arc (in) Leakage (in) Weight Lbs (kg)
S2 40 80 093 VA SS 028 902 768 1486 1549 107.6 93.2 200.4 24.5 (11.1)
S2 40 80 093 VA SS 041 902 768 1486 1549 107.6 93.2 250.8 28.6 (13.0)
S2 40 80 090 VA SS 042 873 746 1442 1504 104.6 90.2 251.7 28.6 (13.0)
S2 40 80 087 VA SS 043 845 716 1398 1460 101.6 87.2 252.6 28.7 (13.0)
S2 40 80 090 VA SS 029 873 746 1442 1504 104.6 90.2 201.3 24.6 (11.2)
S2 40 80 084 VA SS 044 816 695 1354 1415 98.6 84.2 253.5 28.8 (13.1)
S2 40 80 087 VA SS 030 845 716 1398 1460 101.6 87.2 202.1 24.7 (11.2)
S2 40 80 081 VA SS 042 788 674 1310 1370 95.6 81.2 242.7 28 (12.7)
S2 40 80 084 VA SS 031 816 695 1354 1415 98.6 84.2 203.0 24.8 (11.3)
S2 40 80 078 VA SS 043 759 652 1265 1325 92.6 78.2 243.6 28.1 (12.8)
S2 40 80 081 VA SS 029 788 674 1310 1370 95.6 81.2 192.3 24 (10.9)
S2 40 80 075 VA SS 043 730 630 1221 1279 89.6 75.2 240.6 27.9 (12.7)
S2 40 80 078 VA SS 030 759 652 1265 1325 92.6 78.2 193.1 24 (10.9)
S2 40 80 072 VA SS 043 702 608 1176 1234 86.6 72.2 237.6 27.6 (12.5)
S2 40 80 075 VA SS 030 730 630 1221 1279 89.6 75.2 190.1 23.8 (10.8)
S2 40 80 072 VA SS 030 702 608 1176 1234 86.6 72.2 187.1 23.6 (10.7)
S2 40 80 070 VA SS 028 683 594 1146 1203 84.6 70.2 177.4 22.8 (10.4)
S2 40 80 070 VA SS 041 683 594 1146 1203 84.6 70.2 227.8 26.9 (12.2)
S2 40 80 067 VA SS 018 654 571 1101 1157 81.6 67.2 135.6 19.5 (8.9)
S2 40 80 067 VA SS 030 654 571 1101 1157 81.6 67.2 182.1 23.2 (10.5)
S2 40 80 064 VA SS 017 626 549 1056 1111 78.6 64.2 128.7 19 (8.6)
S2 40 80 064 VA SS 028 626 549 1056 1111 78.6 64.2 171.4 22.4 (10.2)
S2 40 80 061 VA SS 016 597 526 1010 1064 75.6 61.2 121.8 18.5 (8.4)
S2 40 80 061 VA SS 026 597 526 1010 1064 75.6 61.2 160.6 21.6 (9.8)
S2 40 80 058 VA SS 017 569 502 965 1017 72.6 58.2 122.7 18.5 (8.4)
S2 40 80 058 VA SS 027 569 502 965 1017 72.6 58.2 161.5 21.6 (9.8)
S2 40 80 055 VA SS 025 540 479 919 970 69.6 55.2 150.7 20.8 (9.5)
S2 40 80 055 VA SS 015 540 479 919 970 69.6 55.2 111.9 17.7 (8.0)
S2 40 80 052 VA SS 016 511 455 872 922 66.6 52.2 112.8 17.8 (8.1)
S2 40 80 052 VA SS 026 511 455 872 922 66.6 52.2 151.6 20.9 (9.5)
S2 40 80 049 VA SS 026 483 431 826 874 63.6 49.2 148.6 20.7 (9.4)
S2 40 80 046 VA SS 025 454 407 779 826 60.6 46.2 141.7 20.1 (9.1)
S2 40 80 049 VA SS 015 483 431 826 874 63.6 49.2 105.9 17.3 (7.9)
S2 40 80 043 VA SS 026 426 382 732 777 57.6 43.2 142.6 20.2 (9.2)
S2 40 80 046 VA SS 015 454 407 779 826 60.6 46.2 102.9 17 (7.7)
S2 40 80 043 VA SS 015 426 382 732 777 57.6 43.2 99.9 16.8 (7.6)
S2 40 80 040 VA SS 015 397 357 685 728 54.6 40.2 96.9 16.6 (7.5)
S2 40 80 040 VA SS 024 397 357 685 728 54.6 40.2 131.9 19.4 (8.8)
S2 40 80 037 VA SS 023 368 332 637 679 51.6 37.2 125.0 18.9 (8.6)
S2 40 80 034 VA SS 021 340 307 589 629 48.6 34.2 114.2 16.2 (7.4)
S2 40 80 037 VA SS 014 368 332 637 679 51.6 37.2 90.1 16.1 (7.3)
S2 40 80 031 VA SS 019 311 281 540 578 45.6 31.2 103.5 17.2 (7.8)
S2 40 80 034 VA SS 015 340 307 589 629 48.6 34.2 90.9 16.2 (7.4)
S2 40 80 028 VA SS 017 283 255 491 527 42.6 28.2 61.7 13.9 (6.3)
S2 40 80 031 VA SS 015 311 281 540 578 45.6 31.2 87.9 15.9 (7.2)
S2 40 80 028 VA SS 009 283 255 491 527 42.6 28.2 61.7 13.9 (6.3)

1)   Electrical Data is with Corona Rings
2)   End fittings for listed catalog numbers = Y-Clevis / ANSI 52-11 Ball
3)   For other ratings or custom insulator designs, contact your local MPS Representative

Scroll to Top